The cable plant "Specresurs" specializes in the production of certified fire-resistant cable lines (FCL)
We offer fire-resistant cable lines (FCL) developed on the basis of cable-carrying systems “DKS” and “Promrukav” using fire-resistant cable products of our own production.
Guarantees of working capacity
The plant guarantees the preservation of the operating time of the FCL in fire conditions while complying with the installation requirements set out in the relevant technical specifications (TS) for products and installation instructions.
Joint testing of all the elements that make up the cable line is the main requirement of regulatory documents when designing an FCL.
The operating time of the FCL is confirmed by a certificate of conformity obtained in accordance with GOST R 53316-2009 “Cable lines. Maintaining working capacity in fire conditions. The test method”.
FCL is designed to ensure the fire safety of facilities, in accordance with the requirements of Federal Law No. 123-FL dated July 22, 2008 (as amended on July 13, 2015) “Technical regulations on fire safety requirements”. Cable lines must remain operational in fire conditions for the time necessary to evacuate people to a safe area and perform the functions of electrical systems operating during a fire.
Our experts will help you choose the optimal fire-resistant cable line.
Contact us to clarify the configuration and calculation of the FCL components of your facility.
Federal Law No. 123-FZ of July 22, 2008 (as amended on 13.07.2015) Technical regulations on fire safety Requirements
“Cable lines must maintain the operability of systems in fire conditions for the time necessary to evacuate people to a safe zone and perform their functions”
Fire alarm system of the facility
Fire warning and evacuation management system
Emergency lighting system on evacuation routes
Water and gas fire extinguishing control system
Smoke protection and ventilation system
Elevators for transportation of fire protection units
Internal fire water pipeline system
FCL operating time
Cable line GOST R 53316-2021
“Clause 3.2 Operability — the ability to continue to perform specified functions when exposed to a standard temperature regime for a specified period of time”
Resistance to Fire Index (REI)
E15
emergency lighting
systems fire warning
systems evacuation management systems
E30
power supply of devices providing evacuation of people from the premises
of the fire warning system, emergency lighting
of the fire alarm system and natural smoke extraction
E45
the same applies in high-rise multi-storey buildings or other structures where people may stay in the evacuation zone for more than 30 minutes
E60—90
emergency elevator power
fire extinguishing systems
supply fire extinguishing systems forced smoke
extraction systems ventilation systems and fire pumps
How to choose FCL
To determine the estimated time required for a complete evacuation at the facility and to determine the estimated time required for the functioning of the systems (maintenance time FCL)
Determine the cable laying method: type of cable-carrying system, open or closed cable laying)
Determine the purpose and brand size of the cable as part of the OKL, the designation of the TS for the cable